Drawing note: member sections and grades are read from the member section table; layout and dimensions from the axis-1 wall purlin plan and the elevation. This batch does not list wall panel type/gauge, insulation, wind load, member lengths or weights; those remain on the original design.
This is the cold-formed and tubular steel framing behind the external wall. Horizontal QLT purlins carry the wall panel to vertical members; ML beams and MZ columns frame door openings; CG struts and Φ12 LG/XLG tie rods brace the wall plane. The elevation is 13,000 mm wide in six bays (2,100 / 2,200 mm), wall top at elevation 12.500 m. Purlins use Q355B; door-frame secondary members use Q235B where listed.

Member Schedule
| Mark | Name | Section | Grade |
|---|---|---|---|
| QLT1 | Wall purlin | C250×75×20×2.0 | Q355B |
| QLT2 | Wall purlin | C250×75×20×2.5 | Q355B |
| QLT3 | Wall purlin | 2C250×75×20×2.2, welded back-to-back | Q355B |
| QLT4 | Wall purlin | 2C250×75×20×2.0, welded back-to-back | Q355B |
| QLT5 | Wall purlin | 2C250×75×20×2.5, welded back-to-back | Q355B |
| QLT6 | Wall purlin | C250×75×20×2.2 | Q355B |
| QLT7 | Wall purlin | Rectangular tube 250×150×5 | Q355B |
| ML1 | Door beam | Rectangular tube 250×150×5 | Q235B |
| ML2 | Door beam | 2C250×75×20×2.2, welded back-to-back | Q235B |
| MZ1 | Door column | 2C250×75×20×2.2, welded back-to-back | Q355B |
| MZ2 | Door column | Rectangular tube 250×150×5 | Q235B |
| MZ3 | Door column | C250×75×20×2.2 | Q355B |
| CG | Strut | Outer Φ32×2, inner Φ12 | Q235B |
| LG, XLG | Tie rod / diagonal tie rod | Φ12 | Q235B |
表格
| Item | Value |
|---|---|
| Wall overall width | 13,000 mm; two 6,500 mm halves |
| Door bay | 300 + 1,400 + 4,800 mm |
| Bay widths (six) | 2,200 / 2,100 / 2,200 / 2,200 / 2,100 / 2,200 mm |
| Elevations | ±0.000, 6.000, 11.105, 12.500 m |
| Vertical zones | 6,000 / 12,500 / 5,100 / 1,400 mm |
| Purlin vertical spacing | 200, 1000, 1250, 1250, 1250, 1250, 1250, 1800, 1150, 1150, 1200, 200 mm |
| Opening offsets | 200, 1,500; 470, 580 mm |
| Axes | 2A/1H, 1G, 1F, 1E, 1D, 1C, 1B, 1A |

How the Wall System Works
Purlins carry the panel. Horizontal QLT C-sections and built-up double-C members transfer wind pressure from the wall panel to vertical framing.
Single and double C match the span. Single C purlins cover regular bays; welded back-to-back 2C members and the 250×150×5 tube carry longer or more heavily loaded runs.
Door frames take opening forces. ML beams and MZ columns form stiff jambs and headers around doors, redistributing loads around the cutout.
Struts and tie rods stabilize the plane. CG struts hold purlin spacing; Φ12 LG/XLG rods brace against out-of-plane wind and erection sway.
The frame ties to the main structure. Wall members connect to building frame columns and beams at the axes shown on the plan.

Advantages
Section range matches demand — 2.0/2.2/2.5 mm C walls, double-C and tube options avoid over-sizing each bay.
Light cold-formed framing — purlins ship flat or bundled and bolt quickly to the main frame.
Regular spacing — six bays at 2.1–2.2 m and repeated vertical purlin lines simplify panel cutting and fixing.
Door openings pre-framed — dedicated MZ/ML members make openings structurally defined instead of cutting purlins on site.
Bracing is itemized — CG struts and Φ12 diagonal rods are marked separately for erection and inspection.
Panel system unspecified here — cladding profile, gauge, liner and insulation are not on these drawings; panel span and fixing must be checked against the purlin spacing.
Wind suction and compression — purlin and brace sizes rely on design wind load; this batch does not state the load.
Double-C welding — back-to-back 2C members need consistent welds and spacing; poor fit-up reduces composite action.
Rod tension and connections — Φ12 tie rods need turnbuckle tension and anchorage; loose rods leave the wall unbraced.
Data gaps on these drawings — member lengths, weights, panel fixings, flashings and base connections are not listed; quantities need the original wall schedule.
Industrial workshop and factory walls on steel portal frames.
Warehouse and logistics building cladding framing.
Steel-framed commercial and exhibition building side walls.
Plant and equipment enclosures with door and ventilation openings.
Retrofit wall infill between existing steel columns and beams.
Verify Q355B and Q235B mill certificates; confirm double-C welds match the listed built-up sections.
Set out the wall from main-frame axes; check the 13,000 mm width, six 2,100/2,200 mm bays and elevations to 12.500 m.
Fix vertical framing first, then single-C purlins; place 2C or tube members only where the plan marks QLT3/4/5/7.
Erect MZ columns and ML beams at openings before cutting panel lines; check header and jamb alignment.
Install CG struts at purlin intersections, then tension Φ12 LG/XLG rods in each braced panel.
Confirm panel profile, insulation, flashing and fastener schedule against the original cladding drawing before closing the wall.
A steel wall framing system: seven QLT purlin types in C250×75×20 sections and one 250×150×5 tube, Q355B purlins, Q235B door-frame and brace members, a 13.0 m wide wall in six bays to 12.500 m elevation, with ML/MZ door frames, CG struts and Φ12 tie rods. Sections and spacing come from the drawings; panel type, insulation, wind load and member weights follow the original wall design.